Legrand AL5200 Series Aluminum Raceway Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Hardware Legrand AL5200 Series Aluminum Raceway herunter. Legrand AL5200 Series Aluminum Raceway User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 2
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
AL5200 ALUMINUM RACEWAY
Installation
Instructions
2"
5"
8.50
sq. in.
Raceway may be configured in single or multiple channels in sev-
eral versatile ways to accommodate power, data or telecommuni-
cations wiring.
NOTE: Cross-sectional area of each compartment indicated.
2 3/16"
3.90
sq. in.
4.50
sq. in.
1 5/8"
2.85
sq. in.
2.85
sq. in.
2.40
sq. in.
1 1/2"
1 5/8"
2.85
sq. in.
5.50
sq. in.
2 3/4"
4.80
sq. in.
3.50
sq. in.
Wiremold Electrical Systems conform with, and should be installed and properly grounded in compliance with requirements of the current
National Electrical Code or codes administered by local authorities. All electrical products may represent a possible shock or fire hazard if improp-
erly installed or used. Wiremold electrical products are UL listed, made for interior use and should be installed by qualified electrical people in
conformance with current local and/or the National Electrical Code.
CAPACITY OF CROSS SECTIONAL AREA
WITH DUPLEX DEVICE (1.34 Sq. In.)
WIRE TYPE 3.5" 3.9" 4.5" 4.8" 5.5" 8.5"
THWN/THHN #6 16 19 24 26 32 55
#8 23 27 34 37 44 76
#10 47 55 68 75 90 155
#12 74 87 108 118 142 244
#14 99 117 145 159 191 329
CAPACITY OF CROSS SECTIONAL AREA
WITHOUT DEVICES
WIRE TYPE 2.4" 2.85" 3.5" 3.9" 4.5" 4.8" 5.5" 8.5"
THWN/THHN #6 18 22 27 30 34 37 42 65
#8 25 30 37 42 48 51 59 91
#10 52 62 76 84 98 104 119 184
#12 82 97 119 133 154 164 188 290
#14 110 131 161 179 207 220 253 391
AL5200 RACEWAY WIRE FILL CAPACITIES FOR POWER
At 90° Outside Corner, position AL5218
External Elbow at end of AL5200B Base.
Slide other base section to other end of
AL5218. Center couplings on joints and
tighten screws. After wiring system,
snap on AL5218 mitered covers.
For retaining wires in long raceway
runs, snap-in AL5200WC Series Wire
Clips into AL5200B Base as required.
Snap AL5206 Cover Clip over joints
in either AL5200B Base or AL5200C
Cover sections.
AL5215 Tee (shown above) and Al5216 Cross: Position fitting at end of
AL5200B Base. Install other base sections to other ends of the fitting. Center
couplings on joints and tighten screws. Install fitting covers after wiring.
AL5200WC
The Wiremold Company
In U.S.:
60 Woodlawn Street • West Hartford, CT 06133-2500
1-800-621-0049 • FAX 860-232-2062
In Canada:
850 Gartshore Street • Fergus, Ontario N1M 2W8
1-800-741-7957 • FAX 519-843-5980
41045 896©1996 The Wiremold Company
For AL5246P Series Device Plates, install wiring to devices as required. Attach
devices to plate using #6 screws and "Keps" nuts provided. Snap device plate onto
AL5200B raceway base.
CAPACITY OF CROSS SECTION AREA*
CABLE/WIRE SIZE O.D. 2.4" 2.85" 3.5" 3.9" 4.5" 4.8" 5.5" 8.5"
UNSHIELDED 4-Pair, 24 AWG, Cat.5 0.220 19 22 27 31 35 38 43 67
TWISTED 4-Pair, 24 AWG, Cat.3 0.190 25 30 37 41 47 50 58 90
PAIR (UTP)
TELEPHONE 2-Pair, 24 AWG 0.140 47 55 68 76 87 93 107 165
3-Pair, 24 AWG 0.150 41 48 59 66 76 81 93 144
4-Pair, 24 AWG 0.190 25 30 37 41 47 51 58 90
25-Pair, 24 AWG 0.410 5 6 8 9 10 11 12 19
COAXIAL RG58/U 18 Gage 0.195 24 28 35 39 45 48 55 85
CABLES RG59/U 22 Gage 0.242 15 18 23 25 29 31 36 55
RG62A/U 20 Gage 0.242 15 18 23 25 29 31 36 55
RG6/U 22 Gage 0.270 12 15 18 20 23 25 29 44
TWINAXIAL 100 Ohm 0.330 8 10 12 13 16 17 19 30
SHIELDED TYPE 1 0.390 6 7 9 10 11 12 14 21
TWISTED TYPE 2 0.465 4 5 6 7 8 8 9 15
PAIR (STP) TYPE 9 0.275 12 15 18 20 23 25 28 44
AL5200 RACEWAY WIRE FILL CAPACITIES FOR DATA/COMMUNICATIONS
1
1
Capacity range is calculated at 40% of raceway areas based on pending changes to the Commercial Buildings Standard for Telecommunication Pathways and Spaces,
EIA/TIA-569. Caution: Capacity for radial bonds reduce to 20% of raceway area.
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - Instructions

AL5200 ALUMINUM RACEWAYInstallation Instructions2"5"8.50sq. in.Raceway may be configured in single or multiple channels in sev-eral versatil

Seite 2 - (optional)

AL5214 Wall Box Connector connects to two in line AL5200B base sections viaAL5201 Couplings supplied.AL5200 BaseDirect FeedFeeding From Wall BoxUsing

Kommentare zu diesen Handbüchern

Keine Kommentare